Skip to content
Official MCP RegistryListed

The New Engineer — HVAC

Part ofThe New Engineer — HVACMCP server

European HVAC sizing: EN 12828 expansion vessels, EN 378 zones, Swiss refrigerant rules.

First seen 2 Oct 2026. Evidence as of 7 Oct 2026.

9
Tools
From an anonymous probe
1
Source listings
Each with its own history
2
Recorded changes
Since first seen

Tools

ToolDescriptionBehaviour
check_en378_zonesDETERMINISTIC: the same inputs always give the same result — from any AI, on any day. Figures come from the standard's tables and formulas, never from a language model's estimate. Every step is auditable. EN 378 applied to BUILDING projects, volume by volume. An installation does not occupy one room but several: the machine, the rooms crossed by refrigerant lines, the rooms served by indoor units. Each volume is classified on its own — access category (a/b/c) and location class (I–IV) — and each classification calls for its own measures. The tool answers per volume, never as a single verdict. It returns, for every volume: its classification and why, the charge limit from Tables C.1 and C.2 of EN 378-1 (with the C.2 formula computed when the table calls for it), whether the charge exceeds it, the EN 378-3 measures that follow, the applicable texts (EN 378-1 to -4, EN IEC 60079-10-1, SUVA 66139 and 2153) and the ventilation flow rates. FOUR CONFIGURATIONS COVER ALMOST EVERY BUILDING PROJECT. Bring the user's case back to one of them wherever possible: machine_en_local_technique chiller or heat pump, all refrigerant inside the machine, standing in a plant room -> c III enceinte_accessible_fermee all refrigerant inside a walk-in ventilated enclosure that stays closed even for maintenance -> the enclosure is c III, the room around it carries no requirement enceintes_inaccessibles one or more units, each in a manufacturer's non-accessible ventilated enclosure -> TWO analyses: the enclosure in operation (class IV, the manufacturer sizes and justifies it, ask him for the enclosure ventilation), and the plant room with the enclosure OPEN for maintenance, which comes back to c III split_traversant split or VRF outdoors, refrigerant lines crossing occupied rooms -> each room on its own; offices and their circulations are b I, and formula C.2 gives the maximum charge for the floor area, or the minimum floor area for the charge THIS TOOL ANSWERS SAFETY IN THE ROOM. It says NOTHING about whether the refrigerant may still be placed on the market or refilled: in Switzerland that is `check_refrigerant_switzerland`. A question that mixes both - « may I use R-32 for 3 kg in a server room, and until when can I refill it » - needs BOTH tools: call this one for the room, and check_refrigerant_switzerland for the dates. Do not answer half the question. NEVER guess. The refrigerant, the configuration and the charge are always needed; a split also needs the floor area and how the indoor unit is mounted (floor, wall, window, ceiling), since C.2 depends on it. Without them the result is `provisional` and carries `questions_to_ask`: ask them, one or two at a time, then call again. Answer from `answer_outline`, volume by volume. In building projects, detection is preferred over treating a plant room as an ATEX zone. C.3 is never used. Say that the practical limit alone proves nothing: the charge limit of Tables C.1 and C.2 is what counts. SCOPE: building services. Cold rooms, food refrigeration and industrial process refrigeration are a different trade. Read-only
check_refrigerant_switzerlandDETERMINISTIC: the same inputs always give the same result — from any AI, on any day. Figures come from the regulation's annexes and thresholds, never from a language model's estimate. Every step is auditable. Swiss refrigerant regulation check (ORRChim / ChemRRV annex 2.10, OFEV synthesis of May 2026, rules adopted 29.10.2025) plus refrigerant data from EN 378-1 Annex E: GWP (AR4, the ORRChim basis), ODP, LFL, safety class, practical limit. Returns, for a given refrigerant and installation: the date from which machines using it can no longer be placed on the Swiss market (import from 01.01.2027, sale to third parties from 01.07.2027), the date from which filling with virgin refrigerant is banned, the period when only reclaimed refrigerant may be used, and the date from which all filling is banned. SCOPE: heating, air conditioning, building cooling and process cooling, data centres included. NOT food refrigeration, cold rooms or deep freezing: those are a different trade, and the tool declines them instead of answering. Use it whenever the user asks about a refrigerant in Switzerland — its GWP / PRG, flammability, whether a chiller, heat pump, split, VRF or cold room using it may still be sold or refilled — in any language: fluide frigorigène, Kältemittel, refrigerante, refrigerant, R-32, R-410A, R-290, CO2, NH3... The answer depends on the installation. The regulation distinguishes: use (building cooling, food refrigeration medium / low temperature / combined / deep freezing, process cooling, heat pump mainly for heating, ice rink), cooling capacity Q0K or heating capacity Q0H, self-contained (factory-built packaged unit) or not, split, direct expansion (incl. VRF), secondary coolant loop (chilled water / brine), air-cooled condenser and refrigerant charge. THIS TOOL ANSWERS ONE QUESTION ONLY: may the refrigerant still be sold and refilled in Switzerland, and until when. It says NOTHING about safety in the room - charge limits, machine room, detection, ventilation, ATEX. That is `check_en378_zones`. A question that mixes both - « may I use R-32 for 3 kg in a server room, and until when can I refill it » - needs BOTH tools: call this one for the dates, and check_en378_zones for the room. Do not answer half the question. NEVER guess these. Call the tool with what the user gave: it returns `provisional: true`, the possible `scenarios`, and `questions_to_ask` in the order that matters most. Ask them (one or two at a time), then call again. Natural refrigerants need no questions. Build your answer on `answer_outline`; quote exceptions as possible, never as granted. Read-only
ifc_upload_resultWhere the upload stands. When `state` is `depose`, `token` is the token to pass to read_ifc_networks.Read-only
name_ifc_networksApply the names you propose, and get back the updated report. THE NAMES ARE YOURS, THE NETWORKS ARE NOT. You are naming what the tool measured; you are not changing what it measured. Nothing you send here alters a network, a part, or a correction. WHAT COMES BACK. The updated report, a 3D link where the user sees your names in colour, and a link to the corrective Dynamo script that writes the systems back into Revit. ALWAYS GIVE THE USER THE 3D LINK, and say plainly which names are yours. Networks are deterministic; names are a proposal. A user who cannot tell the two apart cannot check your work. AFTER THE USER HAS BEEN IN THE 3D VIEW, call read_ifc_networks again with the same token before saying anything about the model. They may have renamed what you proposed, assigned parts by hand, or refused a correction — and only a fresh read shows it. Changes data
open_ifc_uploadShow an upload box in the conversation where the user can drop an IFC file (.ifc) of a building services model (HVAC, plumbing, heating). The file goes straight from the user's browser to thenewengineer.com - you never see it. CALL THIS when the user wants to analyse an IFC model and has not yet given you a link from thenewengineer.com. Then tell the user to drop the file in the box. When the upload is done, the box posts a message with a token. Use that token with read_ifc_networks. If no message arrives and the user says the upload is done, call ifc_upload_result with the upload_token returned here. Prototype: files up to the anonymous size limit of the site.Changes data
read_ifc_networksDETERMINISTIC: networks come from geometry, not from a guess. The same model always gives the same networks, from any AI, on any day. Read the networks of an IFC model already uploaded by the user. WHAT A NETWORK IS. A set of parts that touch each other, cut at equipment: a pump, an air handling unit, a chiller separates two systems, so the tool does not run through them. This is measured on the geometry — you cannot and need not check it. WHAT YOU GET, PER NETWORK state 'homogeneous' — a system exists, some parts were mis-named by the modeller; the tool will correct them. 'undetermined' — no system can be read. THIS is where you are useful. 'assigned' — the user or you already named it. system the dominant name, when there is one part_dominante the share of named parts carrying it equipements_voisins the NAMES of the machines this network is connected to. An undetermined network starting from 'AHU-Supply-L2' names itself — but only you can see it. systemes_existants every system name already in the model WHAT TO DO NEXT. Propose a name for each undetermined network, using the neighbouring equipment, the existing system names, and anything the user told you about the project's naming scheme. Ask the user for their list of planned systems if you do not have it. Then call name_ifc_networks. WHAT NOT TO DO. Do not rename a network the report calls 'homogeneous' unless its name plainly contradicts the equipment it is connected to — and then say why. Do not invent a network: you cannot see the geometry, and the tool already did that work. CALL THIS AGAIN WHENEVER THE STATE MAY HAVE MOVED. The token stays valid for 48 hours and is a key, not a snapshot: every call recomputes and returns the model AS IT IS NOW. The user works in the browser between your messages — renaming networks, assigning parts by hand, accepting or refusing corrections. So the moment they say they have done something, or you are about to state a figure, call this tool again. NEVER ANSWER FROM MEMORY about networks, counts or states. What you read earlier is already out of date the moment the user touches the 3D view, and a stale figure stated confidently is worse than no figure at all. Read-only
read_ifc_overviewCALL THIS FIRST, as soon as the user gives you a token. It answers within seconds, while the network graph is still being built - use that time to think. WHAT YOU GET. Not 3 000 parts: the 20 to 50 distinct TYPES of the model (duct types, fittings, dampers, terminals, equipment, proxies), each with its IFC class, predefined type, type name, one example part with ALL its properties, and a catalogue of every property present. WHAT TO DO WITH IT. Write RULES, not verdicts. For roles: which words, in which field, identify a fire damper, a silencer, a balancing damper, an air terminal, an air handling unit, a fan, a pump - and which groups are NOT network at all (access zones, plinths, placeholders, damper motors). For sizes: which 'PropertySet.Property' holds height, width, diameter, length. A rule applies to every part, including those you were not shown, and to the user's next models. TRAPS the field 'a_savoir' warns about: values are in the FILE's unit (see metres_par_unite), not millimetres; insulation sizes and hydraulic diameters look like dimensions and are not. The field 'etat_du_graphe' says whether the networks are ready yet: 'pret' means read_ifc_networks will answer now.Read-only
size_expansion_vesselDETERMINISTIC: the same inputs always give the same result — from any AI, on any day. Figures come from the standard's tables and formulas, never from a language model's estimate. Every step is auditable. Size the expansion vessel and pressurisation of a closed heating or chilled-water circuit to EN 12828: static height, minimum pressure p0, fill pressure pa, final pressure pe, expansion volume, water reserve, nominal vessel volume with the standard vessel to buy, safety valve setting together with the minimum it must not fall below, pressure class of the lowest equipment, intermediate vessel when needed. Heights become pressures through the real density of the fluid, at the temperature that matters for each: the coldest for p0, the design temperature for the valve and the lowest point. Water and glycols therefore give different figures for the same height. Use it whenever the user asks to size or check an expansion vessel, pressurisation unit, pre-charge pressure or safety valve — in any language: vase d'expansion, maintien de pression, Ausdehnungsgefäss, Druckhaltung, vaso di espansione, vaso de expansión. Needs the installation water volume and THREE heights, all measured from the point where the expansion vessel connects to the network: - the highest point of the installation, above it; - the lowest point, usually below it (negative) or level with it; - the safety valve, which always sits on the heat generator or chiller. If the user does not know it, it is assumed 1 m above the vessel connection, and the result says so. Ask the user for the volume and the three heights before calling. NEVER invent a height: if the lowest point or the valve height is unknown, omit it. The result is then marked provisional and lists the questions to ask. Build your answer on `answer_outline`: it carries the assumptions, the questions and the link to the website, which measures all of these on the user's IFC model. Read-only
water_content_from_vesselDETERMINISTIC: the same inputs always give the same result — from any AI, on any day. Figures come from the standard's tables and formulas, never from a language model's estimate. Every step is auditable. Deduce the water content of an installation from the expansion vessel already fitted. WHAT THIS IS FOR. Refurbishment, and site visits with no drawings. Sizing a new vessel, a new pump or a new generator needs the water content, and on an existing installation nobody has it: the drawings are lost, or never matched what was built. The vessel on the wall is the one piece of evidence still standing, and it was chosen from that very figure. ASK THE OPERATOR FIRST. Whoever filled or refilled the system knows the real figure — from the meter, the filling station, or the maintenance log — and that figure beats any deduction. This tool is what you use when nobody knows, or to check a number that looks wrong. It gets the conversation moving; it does not close it. HOW. The sizing calculation is run backwards: a trial water content is fed to the EN 12828 sizing, the resulting vessel is compared with the one on site, and the trial is adjusted until they match. The formulas are never rewritten in reverse — the answer cannot contradict the direct calculation, because it is the same code. WHAT THE ANSWER IS WORTH. A vessel is picked from a catalogue range: a 200 L unit covers everything needing between 141 and 200 L. The result is therefore A RANGE, never a single figure. And an oversized vessel — common — will overstate the content. Compare the range with what you see on site; it does not replace looking. It also assumes the vessel was sized correctly in the first place. If it was not, the deduction inherits the mistake — which is itself worth knowing: a range far from what the installation plainly holds means the vessel is wrong, and that is a finding in its own right. Read-only

Change history

  1. water_content_from_vessel: input schema changed
  2. read_ifc_overview: tool added
Source listings
SourceListingFirst seenLast seenVersions
Official MCP Registrycom.thenewengineer/hvac2 Oct 20267 Oct 20261